What is Vk and Imag i.e Knee point voltage & Magnetising
Current?
How to calculate above values?
How to define accuracy class 5P10?
Answer Posted / pradeep maurya
Dear friend,
Knee Point voltage is nothing but a point at which the CT
saturates. Thatsy its always better to design the CTs which
can operate without saturation even at a voltage appears in
the CT during fault condition. Pls find below the following
formula for calculating the Knee point voltage.
The formula for Knee Point Voltage is:
Vkp = K * If/CTR * (RCT + RL + RR)
in which,
K = Constant, conventionally taken as 2.0
Vkp = The minimum Knee Point Voltage
If = Maximum Fault Current at the location, in Amperes
CTR = CT Ratio
RCT = CT Secondary Winding Resistnace, in Ohms
RL = 2-way Lead Resistance, in Ohms
RR = Relay Burden, in Ohms
pkmauryain@gmail.com
Is This Answer Correct ? | 0 Yes | 1 No |
Post New Answer View All Answers
On a 3 winding transformer YNynd11, how do you apply REF protection to the Delta tertiary winding that is supplying auxiliaries to a substation?
which book to refer in electrical engineering for iocl exam & which book for general english.
what is the profesional board for electrical engineer what is thepast and during construction for electrical engineering
the site measured knee point voltage of protection class CTs should be greater than rated knee point voltage? what about meetering class CTs. Should it be below the rated knee point voltage?
list the type of vfd? wich is sutable for heating kiln?
How to connect the chemical earthing and complete process tell me plz
Why MCCB is Getting tripped sometimes when there is no load in the Midnight ?
what is the function of choke in the flourcent tube lights and why the colour is in white mostly in flourcent tube lights
I need a formula to calculate the size of cable as per load but in the terms of length. Please Reply me as i search lot of sites but i did not get the answer.
What is Anemometer used to measure?
diameter of cable and core is doubled then the value of capacitance is
at meter room 50 hrc switch installed,but there are not get earthing proper,so what happen?and 11kv transformer out put going in to hrc main 400a three nog each? so earthing is require for all switch? (some customer made earthing at there home.)
What is the difference between PLC and Embeded system
Do closed loop systems require manual input?
how a.c. genarator control power factor when its conected to grid supply by incrising or decresing excitation voltage.