what is the CT of protection and CT of metering ? what is
class 5P10 & 5P20 and class PS ?
Answer Posted / anonymous
CT of protection(PS 5P10 5P20) type is designed for low accuracy and high saturation bcoz at the time of fault curretn is very high. Gives input to relays.
CT of meter(0.1 0.5 1) type is designed for high accuracy and lower saturation. Gives input to ammeters.....
Eg: CT specs 10VA 5P10
This means it has a ratio error of 5% at 10 times rated current I if the real load consumes 10 VA at I.
CT specs 10VA 5P20
Ratio error 5% at 20 times I
Both are same as it gives same ratio error; selection however differs as 5P20 has higher saturation limit
Is This Answer Correct ? | 10 Yes | 6 No |
Post New Answer View All Answers
what is RFCT and Insulgard Relay & It's function?
hi, i have 3x200KVA and 2 x 80KVA UPS with battery bank of 150AH 68Nos. and 100AH 204Nos., i need to install AC either ductable or PAC type, so can you help me to calculate heat load and capacity of the AC to install.
what is the excess air in furnace
How can we calculate the motor frame sizes?
1.how many types of relays? 2.difference between ATS& STS?
what is the difference between transformer,converter and transducer
why capacitive load is not used in routine life????any reason is there ??????
What is the Nyquist criterion regarding control systems?
How colour picturetube works & how many year it will works.
How to select circuit breakers rating eg. if i select a circuit breakers of capacity 40 amps DC with operating voltage 28 volts and if i what to use same circuit breakers for 300 Volts DC application what is the current rating of this circuit breakers.
What is difference between insulating medium and fault current interruption medium in a switching device.
What is the lifetime of a Thyristor? Is there a recommended lifetime for thyristors after which they should be replaced?
What Is HO factor in power selection
at what base you will tell the direction of rotation of dc motors and generators?
1.why we are using blocks in withoutgaplightning arrester 2.why we ar using bushing in withoutgap lightning arrestor