Answer Posted / sangeetha.np
The percentage represents the amount of normal rated
primary voltage which must be applied to the transformer to
produce full rated load current when the secondary winding
is short circuited. The maximum short circuit current that
can be obtained from the output of the transformer is
limited by the impedance of the transformer and is
determined by the multiplying the reciprocal of the
impedance timed the full load current . Thus, if a
transformer has 5% impedance, the reciprocal of .05 is 20
and maximum short circuit current is 20 times the full load
current.
Is This Answer Correct ? | 4 Yes | 2 No |
Post New Answer View All Answers
please send me the previous year's question papers of jindal GET exams
Why do power lines not short out when they fall into water?
1.why should we connect the measuring instruments in l.v side in short circuit test of a transformer? 2.why the power factor is less in open circuit test of a transformer?
my b-tech percentage is 50%. what answer will satisfy the hr ?
Any one who apply for Ferro Scrap Nigam Limited cn join with me at rajuhalder@indiatimes.com or 09669717028
what is the difference between Central Battery System and UPS in applications and uses? and why UPS suitable for Computers and central battery for emergency lighting?
How dia computation perfomed in cold rolling mills .
can we use CBCT in neutral of solidly grounded transformer? in place of three phases we can pass only one phase which decreases the size of CBCT?
What is the loss of power of transformer 220kv/33kv,63/80mva of % imp12.05 at 80%load
What are the section criteria for cables. Now everywhere XLPE power cable is used or PVC is also used?.
Can an inverter be used as a converter? How?
what is apparent poewr, reactive power, & active power?
Dear sir, In our plant have Station Transformer having capacity,i want to know, why LV side 40 - 40MVA is given? & how we can get 6.3 KV supply from tertiary(i.e. Open delta connection), Vector Group YNyn0 - yn0 +d MVA Rating 80MVA / 40 - 40MVA + 26.7MVA Voltage rating 420 (Tap range +6,to -10)81.25% /11.5KV - 11.5KV +6.3KV
why would the rotor rotate at sub synchronous speed against the direction of rotating flux when d rotor of 3 phase IM is connected to 3 phase balanced supply and the stator windings are shortcircuited ??
How to reduce -234126219.6403 MVAr generation and by what?