An electronic p controller has an input range of 1-5v, and
output range of 4-20mA, while testing a step change of 0.4
was applied at the input , the PB setting was 50% ,what
should be the change in the output ?
Answer Posted / abhishekk
as PB is given 50%, so Prop gain would be (100/PB)..in this
case it is twice(prop gain)...now as we know for the change
of 1 v in input we get 4ma change in output..so for 0.4 the
change will be 1.6ma WITHOUT using P controller...BUT we
have Prob gain is 2 so change in output will be 1.6*2=3.2ma
hence change in output is 3.2ma
ok..!!!
Is This Answer Correct ? | 18 Yes | 1 No |
Post New Answer View All Answers
Pressure tx shows 1 mbar but we need 1000 mbar at this process condition .. how can we sort it out .
Introduce yourself which is not present in your biodata?
what is the procedure to callibrate temp controller ,pressure controller,etc. suppose a temp controller showing error 1.5 degree centigrate how can i minimize it.
Hi i am aneesh, done btech in applied electronics & instrumentatiin. And then i took mba in finance & marketing.After that i got placement in finance co and worked there for 3.5 yrs.Now i wanted to come back to engineering job.But without engg experience, i may not able to find an opening.i have done a course related to flow meters and ite calibrations. Kindly suggest where should i try to get a job?
How is work 5/2 sov?
why using negative supply for bentley nevada vibration system ?
Tell me the field calibration procedure step by step with diagram of pressure gauge, pressure switch, pressure transmitter, temperature switch, level switch, flow switch, flow transmitter.
what is loop1 and loop2 in MTS LT?
what is the current pay package for an instrumentation engineer having 2 years of experience in cryogenic technology???????
where proximity sensor installed on tank in loading arm application
we have level transmitter for h2s04 storage tank capacity 10k ,always there are failure of transmitter due to failure of magnetic floats ,please come up with solutions at the earliest.
Tr. Wiring for calibration.
What is 1:1 redundancy ?
How to calibrate radar type level transmitter for interface level? Total liquid(liq.1 and liq.2), level both the liq individually? For. Both the liquid levels how the signal will go from transmitter to dcs? How to calibrate. Single radar 9:26:55 AM for 2 different liquids in a tank?
what is interface level and how it is calibrate?