Assume a condition such that two motors of rating
6.6kv,415v are connected to blower,so tell me which motor
draw large current give appropriate reason?
Answer Posted / pillay
The current drawn depends on the power consumed by the motor
and the operating voltage.
KW =1.72 X VL X IL X PF
Now assuming both the motors are loaded at 100 kw each OF PF
0.8 than the 6.6kv motors current consumption will be
100000KW /1.72 X 6600 X 0.8 =11 AMPS
If 415 volts is used than
100000 / 1.72 x 415 x 0.8 = 175 AMPS.
Is This Answer Correct ? | 17 Yes | 1 No |
Post New Answer View All Answers
for hipot test on 33kV busbar, we will test on 70 kV or 56kV, what is the acceptable leackage current?
Define cuttoff frequency?
How phase to phase voltage comes 440V.
sir i am apearing for nic exam.i dont know exam pattern.can you please send me some model papers
If we have to feed a housing complex having load 8MVA, than what would be the better option, either we first step down 33kv supply into 11kv & than 430v or we proposed no of 33/.44 kv transformer, also which option is economical?
What is the capacity of the Fastners 12mm?
how u select control transformer for a mccb panels or any panels?for expample we hav 440 volts maim supply and control volts is 230v?
15hp motor wound by 0.9mm & 0.95mm magnet wire. at no load test it draw 4.2A current. Another motor with same condition draw 9.2A current. How can that occur? pls help
The D.C. spark test is applicable to single conductor cable & assemblies of insulated single conductor cables without insulation shield,metallic sheath or metalic armor?
which is the best institute for PLC,SCADA,DCS in hyderabad
What is the difference between diesel generator engine with and without turbo charger with the same capacity?
How much current will a 5 HP delta connected motor at no load will take?Is tat need a starter
How can we calculate the transformer rating if the load calculated is 1000KW (11Kv Supply)?
What is the importance of earthing?
What is the physical significant of power factor?