What core magnetic balance test of transformer?
How to do this test in a three phase Star delta (star-LV,
Delta-HV) transformer?
How to measure and where to measure?

thanks and regards
Austin

Answer Posted / engr. ziaul ashraf shafi

Answer #5 is fine.. but i want to add something more..
normally this test is made in star side of the transformer.
the result should be varified like following:
1) if 2u-2n is fed by 230 volt.
- the nearest phase (2v-2n) will experience the 85% to 90%
of fed voltage at 2u-2n. (i mean 2v-2n = 195.5 to 207
volt). And the distant phase (2w-2n) will experience the
10% to 15% of fed voltage at 2u-2n. (i mean 2w-2n = 23 to
34.5 volt).
2) if 2v-2n is fed by 230 volt.
- then the fed pahase is middle phase, and both other phase
are magnetically in equal distance.. so the measured
voltages in 2u-2n or 2w-2n = 50 % (or 40 to 60 % is also
accaptable). so the 2u-2n or 2w-2n = 92v to 138v is
accaptable.
3) if 2w-2n is fed by 230 volt.
- the nearest phase (2v-2n) will experience the 85% to 90%
of fed voltage at 2w-2n. (i mean 2v-2n = 195.5 to 207
volt). And the distant phase (2u-2n) will experience the
10% to 15% of fed voltage at 2u-2n. (i mean 2w-2n = 23 to
34.5 volt).

*If the results are found beyond these above mentioned
limits then other tests (like open ckt test with rated
voltage) should be performed to be sure about core and
winding.
*You can measure and note down the current of each injected
phase. it will give u a signaficant idea about winding. if
the winding has an inter-tern short then the faulty phase
will draw comapretively large magnetizing current like 3A
or 5A, wheather other phases will draw 60mA to 100mA.
*Remember, the magnetic reluctance path of a core is not
lenier, so the result veries itself. But big differences
are remarkable.
*Sometime due to non-lenier characteristic of magnatic
circuit and the presense of harmonics in the fluxes of un-
excited phases, the algebric sum of induced volage in two
phases may not be equal to the applied voltage.
*if there is a turn to turn fault in any phase winding, the
faulty section will draw comparetively large magnatizing
current which will oppose the magnetic fluxes and will
result a very low induced voltage (tends to zero) in the
faulty phase.
*this test should be performed after demagnaizing the
transformer properly. slightly magnatized transformer (like
after insulation test) can give you an unexpacted and
distorted result of magnetic balance test.

Is This Answer Correct ?    73 Yes 3 No



Post New Answer       View All Answers


Please Help Members By Posting Answers For Below Questions

WHAT IS SUBSTATION & ACCORDING TO VOLTAGE HT,EHT SUBSTATION EXPLAIN IT

2697


write encoder 17 pins details? pin a;b+, pin b;w+,..pin s & t. what is the meaning of b+, w+? explain;

1696


what is meant by carrier aided trip protection in transmission line

3318


Why are cables rated for 40 KA for 0.25 Sec fault current rating?

1522


derive DC RMS value for half wave rectifier?

2720






33kv substation lay out details & line to line & line to earth measurements

2170


concept of busbar and load dispatching..?

1931


Why induction motor is widely used in industry

2267


Why do you have to use Protecion relay with the function MTB ( Mechanical Trip Button ) for electrical system.

1710


HOW WE KNOW IN PHYSICALLY THE CONTACT SURFACE OF A VACUUM INTERRUPTER IS GOOD OR GOING TO DAMAGE IN A VCB AFTER ABOVE 500 TIMES OPERATED.

1654


how to calculate differential current when we testing differential relay..suppose we have 1000kw generator,630amp VCB,what value we should put /inject so that relay trip the VCB? PLLZ justify ur comment

1168


difference between ac series and parallel circuit

1475


A d.c. Shunt motor is found suitable to drive fans because they require?

740


What does Bode plot tell you?

814


can anyone explain 11kV 3core cable megger,hi pot test procedure with connection details?

2802