What are the causes of boiler backfire and steps in how to
prevent it from happening?
Answers were Sorted based on User's Feedback
Answer / viraf b. karanjawala
the probable causes of boiler backfire are 1) outlet damper
partially/fully closed, 2) Improper tuning of the burner 3)
accumulation of combustible gases in pockets with in the
furnace 4) accumulation of unburnt fuel left in the furnace
5) purging time before and after burner shut off not enough
i.e. too short, 6) vol of the gases against vol provided by
the boiler manufacturer
Is This Answer Correct ? | 53 Yes | 7 No |
Answer / jose thomas
1. Unburnt fuel leftover in the furnace during previous
operation.
2. Fuel leak to the furnace before ignition.
3. Presence of flue gases in furnace.
4. Pre-purge and post-purge timings are not enough.
5. Incorrect burner settings.
6. Improper ratio of fuel and air volume.
7. Burner malfunctioning /Controller malfunctioning.
8. Outlet damper less opened.
Is This Answer Correct ? | 35 Yes | 0 No |
Answer / m.abbas
1-Unburnt fuel accumulation in the furnace
2-Repeated unsuccessful strat attempts for boiler firing
3-Burner malfunction and air fuel ratio disturbance
4-Inadequate pre and post purging
5-Flue gases outlet damper malfunction
Is This Answer Correct ? | 27 Yes | 3 No |
Answer / salai jeyaveeran
the basic thing for backfire in a boiler is occurance of
positive pressure in a furnace (or) boiler this can be
happend due to
high flow from FD
partial open in ID damper
low RPM of ID fan
punture of tubes
Is This Answer Correct ? | 19 Yes | 7 No |
which power station plants r more efficient? which is less? which is most expensive and which is cheapest?
What materials are used for engine propeller?
what is advantage and disadvantage of forward curve and backward curve blade of an id fan impeller and FD fan impeller??
Name the types of welding?
wt is powder coating ?wt r the guages used to check powder coating ?
In 1983 what changed about the length of the meter?
SIR I M STUDENT OF POWER ENGG CAN I GIV PSU XAM 4 NTPC AND WHAT WOULD B THE PROCEDURE
Why should we hire you over the others waiting to be interviewed?
Whether entropy is intensive property or extensive property ?
Anybody please send me the papers of the reliance exam (apti and tech) so that i can go through it) mail me at raminder_verma@rediffmail.com
sir I have applied for HPCL management trainee..Can i get previous MECHANICAL ENGINEERING question paper..? stalin
3 Answers Bhel, HPCL, IOCL, RRB,
"In electricity, what is commutator? Carbon brush? "